WATER MIST EXTINGUISHER 09 LTRS CAPACITY (BACK PACK TYPE/ HIGH PRESSURE)
Category: Forest Fire Equipment
Color: Red,
Size: ,
Parameters Technical Specifications Trial Directives
1. Nomenclature/ Name
product/gadget/
equipment
High pressure water mist CAF fire extinguisher Back- pack
type, ultra-light, Carbon composite with Pet liner pressure
vessel 9 ltrs and air cylinder.
To be checked physically by BOOs.
2. Conformity The Water Mist & CAF(Back Pack) high pressure extinguisher
shall be confirmed to EN 3- 7:2004+A1:2007-08 standards The
complete system shall be tested for compliance from an
internationally/ nationally accredited laboratory for compliance
to all 30 clauses (3.2, 3.15, 4.2, 4.3, 4.4, 4.5, 6.1, 6.2, 6.3, 7.1.1,
7.1.2, 7.2, 7.3, 7.4, 8.1, 8.2, 9.2, 10.1, 10.2, 10.3, 10.4, 10.5,
10.6.1 & 10.6.2, 14.1, 14.2, 15.2, 15.3, 16.1, 16.2) of EN 3-
7:2004 + Al: 2007-08 (E) Standard mandatorily applicable for
the complete system."
To be checked and verified with relevant
EN certificates.
3. Mounting type Backpack To be checked physically by BOOs.
4. Configuration/ Description It shall be mounted on a sturdy frame suitably cushioned for
comfort, provided with shoulder pads for carrying as a BOOs.
Backpack and a handle to be carried by hand. All materials used
shall be of fire retardant type. Backpack shall be supplied with
air cylinders.
To be checked physically by the BOOs.
5. Model & make Model Number shall be permanently marked as declared in
Accredited Laboratory Test Report.
To be checked physically and verified with
relevant certificates by the BOOs.
6. Main Components: Pressure vessel shall be hold the media with safety valve,
compressed air cylinder coupled with a reducer, hose pipes for
discharge of water mist media, extinguishing gun.
To be checked physically by the BOOs.
7. Air Cylinder Material Ultra-light Carbon composite with PET To be checked and verified with relevant
EN & PESO certificates.
8. Type of Foam Standard AFFF Compound conforming for higher fire rating
A55, B233, Spreading coefficient for Standard AFFF
Compound shall be +5 minimum, concentrations shall be 6%.
To be checked and verified with relevant
certificates from Govt./NABL accredited
lab.
9. Commercial Brand Name,
laboratory test report/ fire
ratings with foam
Commercial Brand Name of the Standard foam (fire
extinguishing medium) as per accredited laboratory test report
wherein higher fire ratings i.e A55, B233, E1000 V (Die
Electric Suitability) achieved, to be declared.
To be checked and verified with relevant
certificates from Govt./NABL accredited
lab.
SNo. Parameters Technical Specifications Trial Directives
10. Characteristics of
extinguishing medium
AFFF Compound with
infrared spectrogram (to be
furnished).
Characteristics of extinguishing medium of Standard AFFF of
Compound shall be- Density: 1.04 (kg/cm³, Viscosity: 1.35
(m²/s, pH Factor 7.8, Refractive Index 1.34 @ 20 +/- 2°C
(accredited laboratory test report required)
To be checked and verified with relevant
certificates from Govt./NABL accredited
lab.
11. Pressure Vessel Material &
Capacity (Nominal Charge)
Ultra-light Carbon Composite with PET Liner of 9 liter
capacity.
To be physically checked and verified with
relevant certificates by the BOOs.
12. Extinguishing gun material Stainless Steel To be checked and verified with relevant
certificates.
13. Weight of extinguishing
gun
Shall not more than 800 gram. To be checked physically by BO0s.
14. Length of standard of Hose
for backpack system
Hose shall be EN marked, not less than 1.3 meters for backpack
system.
To be checked physically and verified with
relevant certificates by BOOS.
15. Weight of fully charged
Backpack system
Weight of fully charged Ultra-light Carbon composite with PET
liner Backpack system shall be not more than 20kg.
To be checked physically by BOOs.
16. Air Cylinder Capacity
(Ltrs)
2 litre To be checked physically by BOOs.
17. Air Cylinder pressure (Bar) 300 bar To be checked physically by BO0s.
18. High Pressure Type High Pressure Type (Dynamic Operating pressure to be tested
in the accredited laboratory test report which will be considered
as high pressure for as per clause No. 3.15 of EN 3-7:2004 +
Al: 2007-08 (E) Standard.) ≥ 37.6 Bar for Ultra-light Carbon
composite with PET Liner vessel.
To be checked and verified with relevant
EN certificates
19. Lancing Distance of Gun More than 15+/-2 meter To be tested physically by BOOs.
20. Minimum operating time 25+/-2 second To be tested physically by BOOs.
21. Operating temperature System shall be designed for 60°C or more and minimum 5º C
or less and certified by the manufacturer as per Clause 7.4 of
EN 3-7:2004+A1:2007-08 standards as per the accredited test
report for backpack system.
To be checked and verified with relevant
certificates.
SNo. Parameters Technical Specifications Trial Directives
22. Fire Rating Class A, Class B and Electrical Fire Rating with standard AFFF
Compound for backpack 55A, 233B, E1000V (Die Electric
suitability) with commercial brand name of fire extinguishing
medium as per accredited laboratory test report for Backpack
System.
To be checked and verified with relevant
certificates of EN.
23. Approval PED (Pressure Equipment Directives) approval as per
2014/68/EU (Encumbrance Certificate).
To be checked and verified with relevant
certificates as per EN by BOOS.
24. Pressure Gauge Pressure Vessel shall be fitted with a pressure gauge (CE
Marked).
To be checked physically with relevant
certificates.
25. NOC certificate) (No
objection
Air cylinder and its valve & Pressure Vessel containing body
No. from Petroleum and Explosives Safety Organization
(PESO)/approval of CCE Nagpur is mandatory.
To be checked and verified with relevant
certificates.
26. Pressure Vessel Pressure Vessel shall be CE marked from Notified body. To be checked and verified with relevant
certificates
27. Consent from OEM Specific consent of the OEM for the value additions made
along with a confirmation that fire ratings of the equipment
would not be affected by these value additions.
To be checked and verified with relevant
certificates.
28. Test Reports Test Report No. should be declared/ mentioned with date. To be checked and verified with relevant
certificates as per EN.
29. Declaration about Govt.
Accredited Laboratory
where Test Conducted
Name of ILAC/ NABL/ Central Govt. Accredited Laboratory
where Test Conducted is required.
Firm to submit certificates from
NABL/International lab for confirming.
30. Pre dispatch inspection Pre Dispatch Inspection (PDI) of product shall be carried out
by CISF Fire/Delhi Fire/NDRF officers as per specification, at
the vendor site where all the testing facilities are available.
To be carried out by BO0s at vendor's site.